Rockwell AOI 2.0 - Controller Setup

Modified on Tue, 22 Jun 2021 at 10:36 PM

Overview





Step-by-Step guide


Step 1 - Upload a new project into Wincaps III from robot controller

Connect Ethernet cable from your computer to the robot controller “LAN” port (not EtherNet/IP card port)


Create a new Wincaps III Project ‐> Change User Level to 1 – Programmer ‐> Press Shift + Down for Password

Go to “File” ‐> New Project ‐> Get information from controller ‐> Next
Input a Project Name and File save location ‐> Click on Next

Input the controller IP Address (192.168.0.1 – Default) ‐> Click Next
Confirm PC IP address is on same network as controller (192.168.0.XXX)
Go to “File” ‐> New Project ‐> Get information from controller ‐> Next

Select “Receive data from the controller” ‐> Click Finish


Step 2 - Generate Command slave license and activate in the controller

Go to the Denso Wave website and login https://www.denso‐wave.com/en/robot/index.html (if new user then please register first)
Select Member menu ‐> RC8 Free license Confirmation
Select “Command‐Slave” in the Product Name drop down list and Enter your controller serial # ‐> Click Send
Go to teach pendant “home” screen ‐> Setting ‐> Option ‐> Extension


NOTE 
If “Option” or “Extension” category is not available, then check login level is “Programmer” – refer to manual on how to change login.

Scroll down until you see “Command‐Slave” under “Func” category and click “Add”

Input license key from website ‐> Click ‘OK” ‐> Verify that status is enabled

 

Step 3 - Download the AOI library and associated manuals

Go to the Denso Wave website and login https://www.denso‐wave.com/en/robot/index.html

Select “Downloads” ‐> “Application Software” ‐> Command‐Slave
Select and download the 3 items starting with “Rockwell Automation” ‐> Save them to your PC

 

NOTE: 
The RC8 Controller firmware version must be 2.5.5 or higher to use this version of
Rockwell AOI.

 

NOTE: 
The RC8 Controller must have an Ethernet IP communication card installed in it to use this version of Rockwell AOI.

 

Step 4 - Set Controller parameters for Ethernet IP connection and Command slave

1. Open Wincaps III project...
2. Select “Project” ‐> Properties ‐> Open I/O Tab
3. Select Device: EtherNet/IP Adapter
4. Select Mode: Standard Mode
5. Select I/O Power source: Internal or external
6. Select desired I/O Size in bytes (Max recommended)
7. Select desired Comm. Speed (Auto‐Negotiate is best)
8. Select Manual IP address for EtherNet/IP I/O card
(different IP address then controller LAN port)
9. Click “OK”


NOTE:
Allowable Input size range is 256‐496 bytes. Allowable Output size range is 256‐500 bytes. The input size is 4 bytes shorter due to the input header shift required with Rockwell PLC.

 

Select “Project” ‐> Parameters ‐> Click on I/O Section

Scroll down to Parameter 128 “Command‐Slave Start” and select “2” for version 2.0 in the drop-down menu


NOTE:
Scroll down to Parameter 160 “EtherNet/IP Input Run/Idle Header” and change to value “1” ‐> Click OK


Scroll down to Parameter 160 “EtherNet/IP Input Run/Idle Header” and change to value “1” ‐> Click OK
NOTE: 
Rockwell PLC requires Input Header shift, but not all PLC require this shift. 
Please check PLC provider manuals for specific requirements on header shift.


Step 5 - Download parameter changes to the Controller

Select “Connect” ‐> Transfer Data

Select I/O Parameters on Wincaps III side ‐> Click Send (sends data from Wincaps file to robot controller)

After download is complete, the controller will need to be rebooted


NOTE:
If an error occurs during download, please confirm pendant screen is on the home page (Press “Cancel” until home screen appears and retry)


Next Steps


Owner's Manual Reference

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select atleast one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article