Problem
If you see the following error this means that within your project the designated field bus is not set correctly.
Related Error codes:
8150202C
Solution
To correct this error you will need to first open a fresh version of your Wincaps III project.
To correct this error you will need to first open a fresh version of your Wincaps III project. Then you will go to Project -> Properties | |
Then select the I/O tab at the top and click on the drop-down arrow next to “Device” Select the field bus card you have installed in your controller. If you do not have an additional card installed (DeviceNet, Ethernet IP, CC-Link, etc.) then you will need to select “Mini IO” and then click “OK”. | |
Then go to Connect -> Transfer Data -> Extend “Parameter” and check the I/O box -> Click “Send” Once you have completed downloading your changes you will need to reboot your controller. The error should be gone once the controller reboots |
Owner's Manual Reference
https://www.fa-manuals.denso-wave.com/en/usermanuals/001061/